Choose your country
Go to your local Sikla page and discover offers for your country or sales region:
Country


Group: 1260
Part number 110336
This is a replacement for Old Productname (Part number 123456).
For high static requirements in plant constructions, design similar to DIN 3567
Holes for standard tensioning bolts and anchors without loss of load capacity
Login to see prices and availabilities
Login or register
B1 | 341 mm |
b1 | 50 mm |
D | 254 mm |
D1 | 254 mm |
d | 13 mm |
e | 308 mm |
H | 270 mm |
t | 8 mm |
Two-piece pipe clamp delivered without bolts.
For suitable bolts, please see catalog.
-VZ,perm. | 42,00 kN |
Admissible load valid with fixation on both sides.
The max. permissible load capacity of the connected parts (e.g. anchors) shall be considered.
The max. adm. load capacity is determined by the application of statistical methods resulting from the breaking loads, under observance of a max. adm. deformation of 1.5 mm resp. 2% of the max. stretchable pipe dia.
Primary element material | steel |
Surface finish | uncoated |
Corrosion protection class | C2 |
Certification

Tightening torque and recommended clamping bolts:
| Size range [mm] | Recommended clamping bolts | Tightening torque [Nm] |
|---|---|---|
| 14 - 49 | M10 x 40 | 20 |
| 57 - 109 | M12 x 45 | 40 |
| 109 - 163 | M12 x 50 | 40 |
| 163 - 273 | M12 x 55 | 40 |
| 317 - 374 | M16 x 60 | 100 |
| 397 - 610 | M16 x 65 | 100 |
PDF (0.23MB)