Choose your country
Go to your local Sikla page and discover offers for your country or sales region:
Country
124 - 318 mm


Group: 1241
Part number 107486
For secure installation of pipes in M&E services – robust and reliable.
Ideal for increased sound insulation requirements.
Complies with DIN 4109 and supports compliance with structural sound insulation requirements.
Login to see prices and availabilities
Pipe Clamp Stabil D3G with Lining – RAL-GZ 655
PDF (203 KB)

B1 | 355 mm |
b2 | 48 mm |
D | 273 mm |
D2 | 273 mm |
e | 326 mm |
Ma | 1/2" |
H | 319 mm |
Mi1 | M12 |
Mi2 | M16 |
t | 4 mm |
-VZ,perm. | 7,50 kN |
Fire Resistance 30 min | 2,4 kN |
Fire Resistance 60 min | 1,4 kN |
Fire Resistance 90 min | 1 kN |
Fire Resistance 120 min | 0,85 kN |
Primary element material | steel |
Isolating element material | SBR/EPDM |
Connecting element material | steel |
Surface finish | electro galvanized (Fe//Zn) |
Corrosion protection class | C2 |
For further adapter-based connection options via the external thread of the 3G triple thread nut, see product "Adapter AD f/f" (this chapter).
For FM applications, at least M10 must be used.
For VdS applications > 2“ to 4”, at least M10 must be used.
| Size [mm] | Tightening torque [Nm] |
|---|---|
| 14 - 23 | 2 |
| 24 - 65 | 2 |
| 67 - 115 | 3 |
| 124 - 162 | 5 |
| 165 - 214 | 10 |
| 219 - 318 | 10 |
Certification